Arcones, EduardoAutor (correspondència)Alvarez, FernandoAutor o coautorKhamlichi, AbderrahimAutor o coautorGarnacho, FernandoAutor o coautorScale Modular Test Platform for the Characterization of PD Measuring Systems Using HFCT Sensors
Publicat a:Sensors. 24 (5): 1363- - 2024-03-01 24(5), DOI: 10.3390/s24051363
Autors: Arcones, E; Alvarez, F; Khamlichi, A; Garnacho, F
Afiliacions
Resum
Today, online partial discharge (PD) measurements are common practice to assess the condition status of dielectrics in high-voltage (HV) electrical grids. However, when online PD measurements are carried out in electrical facilities, several disadvantages must be considered. Among the most important are high levels of changing electrical noise and interferences, signal phase couplings (cross-talk phenomena), and the simultaneous presence of various defects and difficulties in localizing and identifying them. In the last few decades, various PD-measuring systems have been developed to deal with these inconveniences and try to achieve the adequate supervision of electrical installations. In the state of the art, one of the main problems that electrical companies and technology developers face is the difficulty in characterizing the measuring system's functionalities in laboratory setups or in real-world facilities, where simulated or real defects must be detected. This is mainly due to the complexity and costs that the laboratory setups entail and the fact that the facilities are permanently in service. Furthermore, in the latter scenario, owners cannot assign facilities to carry out the tests, which could cause irreversible damage. Additionally, with the aforementioned installations, a comparison of results over time in various locations is not possible, and noise conditions cannot be controlled to perform the characterizations in a correct way. To deal with the problems indicated, in this article, an affordable scale modular test platform that simulates an HV installation is presented, where real on-site PD measuring conditions are simulated and controlled. In this first development, the HV installation comprises a cable system connected at both ends to a gas-insulated substation (GIS). As the most common acquisition technique in online applications is based on the placement of high-frequency current transformer (HFCT) sensors in the grounding cables of facilities, the test platform is mainly adapted to carry out measurements with this type of sensor. The designed and developed test platform was validated to assess its features and the degree of convergence with a real installation, showing the convenience of its use for the appropriate and standardized characterization of PD-measuring systems.
Paraules clau
Indicis de qualitat
Impacte bibliomètric. Anàlisi de la contribució i canal de difusió
El treball ha estat publicat a la revista Sensors a causa de la seva progressió i el bon impacte que ha aconseguit en els últims anys, segons l'agència Scopus (SJR), s'ha convertit en una referència en el seu camp. A l'any de publicació del treball, 2024 encara no hi ha indicis calculats, però el 2023, es trobava a la posició , aconseguint així situar-se com a revista Q1 (Primer Cuartil), en la categoria Instrumentation.
Independentment de l'impacte esperat determinat pel canal de difusió, és important destacar l'impacte real observat de la pròpia aportació.
Segons les diferents agències d'indexació, el nombre de citacions acumulades per aquesta publicació fins a la data 2025-06-17:
- WoS: 3
- Scopus: 5
- OpenCitations: 4
Impacte i visibilitat social
Anàlisi del lideratge dels autors institucionals
Hi ha un lideratge significatiu, ja que alguns dels autors pertanyents a la institució apareixen com a primer o últim signant, es pot apreciar en el detall: Primer Autor (ARCONES DEL ALAMO, EDUARDO) i Últim Autor (GARNACHO VECINO, FERNANDO).
l'autor responsable d'establir les tasques de correspondència ha estat ARCONES DEL ALAMO, EDUARDO.