Arcones, EduardoAutor (correspondencia)Alvarez, FernandoAutor o CoautorKhamlichi, AbderrahimAutor o CoautorGarnacho, FernandoAutor o CoautorScale Modular Test Platform for the Characterization of PD Measuring Systems Using HFCT Sensors
Publicado en:Sensors. 24 (5): 1363- - 2024-03-01 24(5), DOI: 10.3390/s24051363
Autores: Arcones, E; Alvarez, F; Khamlichi, A; Garnacho, F
Afiliaciones
Resumen
Today, online partial discharge (PD) measurements are common practice to assess the condition status of dielectrics in high-voltage (HV) electrical grids. However, when online PD measurements are carried out in electrical facilities, several disadvantages must be considered. Among the most important are high levels of changing electrical noise and interferences, signal phase couplings (cross-talk phenomena), and the simultaneous presence of various defects and difficulties in localizing and identifying them. In the last few decades, various PD-measuring systems have been developed to deal with these inconveniences and try to achieve the adequate supervision of electrical installations. In the state of the art, one of the main problems that electrical companies and technology developers face is the difficulty in characterizing the measuring system's functionalities in laboratory setups or in real-world facilities, where simulated or real defects must be detected. This is mainly due to the complexity and costs that the laboratory setups entail and the fact that the facilities are permanently in service. Furthermore, in the latter scenario, owners cannot assign facilities to carry out the tests, which could cause irreversible damage. Additionally, with the aforementioned installations, a comparison of results over time in various locations is not possible, and noise conditions cannot be controlled to perform the characterizations in a correct way. To deal with the problems indicated, in this article, an affordable scale modular test platform that simulates an HV installation is presented, where real on-site PD measuring conditions are simulated and controlled. In this first development, the HV installation comprises a cable system connected at both ends to a gas-insulated substation (GIS). As the most common acquisition technique in online applications is based on the placement of high-frequency current transformer (HFCT) sensors in the grounding cables of facilities, the test platform is mainly adapted to carry out measurements with this type of sensor. The designed and developed test platform was validated to assess its features and the degree of convergence with a real installation, showing the convenience of its use for the appropriate and standardized characterization of PD-measuring systems.
Palabras clave
Indicios de calidad
Impacto bibliométrico. Análisis de la aportación y canal de difusión
El trabajo ha sido publicado en la revista Sensors debido a la progresión y el buen impacto que ha alcanzado en los últimos años, según la agencia Scopus (SJR), se ha convertido en una referencia en su campo. En el año de publicación del trabajo, 2024 aún no existen indicios calculados, pero en 2023, se encontraba en la posición , consiguiendo con ello situarse como revista Q1 (Primer Cuartil), en la categoría Instrumentation.
2025-05-18:
- WoS: 3
- Scopus: 4
- OpenCitations: 4
Impacto y visibilidad social
Análisis de liderazgo de los autores institucionales
Existe un liderazgo significativo ya que algunos de los autores pertenecientes a la institución aparecen como primer o último firmante, se puede apreciar en el detalle: Primer Autor (ARCONES DEL ALAMO, EDUARDO) y Último Autor (GARNACHO VECINO, FERNANDO).
el autor responsable de establecer las labores de correspondencia ha sido ARCONES DEL ALAMO, EDUARDO.